Is it possible to replace the electric lock wire with a network cable
2016-11-09 16:23
Details of the problem:

We use a network cable to wire the electric lock to the controller, what is the problem? I heard that if the network cable has been used for a long time, there will be problems?

Expert answer:

The section of wire from the electric lock to the controller in the access control construction looks very ordinary, if it is not standardized, it will easily cause failures that are difficult to find the cause, this must be paid attention to!

Due to the relatively large operating current of the electric lock (compared to other devices of the access control system, such as the controller card reader), the electric lock is at a certain distance from the controller, and the voltage drop on the line will be relatively large. If the voltage drop is too large, the electric lock will sometimes be able to move, and sometimes not. Magnetic locks sometimes have insufficient suction power. Shows that the door switch is abnormal. It may even grab current resources with the controller, making the controller insufficient power supply, restarting or even crashing.

Some engineers are eager to make wiring convenient for a while, or convenient to purchase, and use network cables to wire the electric lock to the controller, which is very easy to cause failure, although there seems to be no problem when debugging, after a period of time, problems will often occur.

For the cable from the electric lock to the controller, if the cable length is less than 50 meters, it is required to use a two-core power cable with a cross-sectional area of 1.0 square millimeter, without shielding, if it exceeds 50 meters, please double cloth and add a two-core power cord to supply power in parallel. If the cable length is greater than 100 meters, it is recommended to move the controller closer to the door electric lock to shorten the wiring distance. The cross-sectional area of the network cable is 0.2 square millimeters, which is 5 times smaller than our standard wire, so it is absolutely impossible, even if the distance between the controller and the electric lock is very short. The electric lock door magnetic signal line can be a network cable. Some people combine the four strands of the network cable to power the electric lock, although it is close to the norm in theory, it is not recommended. Doing so will cause other hidden dangers such as unstable connection terminals.

Stephanie Stephanie Stephanie Ellie Ellie Ellie Victoria Victoria Victoria Olivia Olivia Olivia Isabella Isabella Isabella Jayden Jayden Jayden Lucas Lucas Lucas Dylan Dylan Dylan Ryan Ryan Ryan Noah Noah Noah

Sweep the concern Yingze electronic official WeChat

x
Sample Apply
※ Please fill in your information, our company will deal with your problem as soon as possible.
主站蜘蛛池模板: 亚洲国产成人精品小蝌蚪 | 这里只有精品国产 | 国产精品欧美亚洲韩国日本99 | 1024国产看片在线观看 | 99久9在线视频 | free麻豆| 一道精品视频一区二区三区图片 | 白丝丝袜高跟国产在线视频 | 香港三级理论在线观看网站 | 日韩毛片欧美一级a | 亚洲国产精品成人午夜在线观看 | 热久久综合这里只有精品电影 | 爱爱免费看| 搜索毛片 | 色cccwww在线播放 | 关婷哪一级毛片高清免费看 | 中文字幕在线永久视频 | 国产a级精品特黄毛片 | 激情婷婷在线 | 北岛玲日韩精品一区二区三区 | 26uuu精品一区二区 | 不卡一级aaa全黄毛片 | 女人被狂躁视频免费版 | 午夜a一级毛片一.成 | 中国一级淫片aaa毛片毛片 | 日本在线观看免费看片 | 国产一级一级毛片 | 直接看毛片 | 欧美亚洲综合另类 | 第一福利在线 | 伦理片一级 | 国产毛片视频 | 欧洲欧美人成免费观看 | 国产伦子一区二区三区四区 | 激情网址在线观看 | 欧美激情首页 | 性欧美高清come | 国产精品亚洲一区二区三区 | 国产精品冒白浆免费视频 | 精品国产综合成人亚洲区 | 日本黄色高清 |